32 R
EFERENCE
& I
NSTALLATION
M
ANUAL
9.11 A
UTO
T
EST
R
EPORT
The control panel can transmit the test report code programmed into
section [3902] every hour (Hourly Test Transmission) or after a period of
time (Auto Test Report Period).
9.12 D
ISARM
R
EPORTING
O
PTIONS
(Default = disabled) When option [7] is disabled, the control panel sends
the Disarming Report Codes (see section 9.2) every time the partition is
disarmed. When option [7] is enabled, the control panel sends the
Disarming Report Codes to the Monitoring Station only when the partition is
disarmed following an alarm. Select the section that corresponds to the
desired partition and enable or disable option [7]:
9.13 Z
ONE
R
ESTORE
R
EPORT
O
PTIONS
(Default = disabled) When option [8] is disabled, the control panel sends
the Zone Alarm Restore report codes to the Monitoring Station when the
Bell Cut-Off Timer elapses (see section 8.2) or when the alarm is disarmed.
When option [8] is enabled, the control panel sends the Zone Alarm
Restore report codes (see section 9.2) to the Monitoring Station as soon as
the zone returns to normal (zone closure) or upon disarming.
9.14 A
UTO
R
EPORT
C
ODE
P
ROGRAMMING
When using either the Contact ID or SIA Reporting Formats (see section
9.6), the control panel can automatically program a set of default report
codes. However, the Contact ID Reporting Format can be modified using
the manual programming method (see section 9.6.3 & section 9.6.4) to
program remaining report codes or to change some of the defaults. From
programming mode (see section 4.4) enter any of the following sections to
set the indicated report codes with the default values (FF) from the
Automatic Report Codes List in the Programming Guide:
Option Feature Description
[3] [4]
OFF OFF
Auto Test
Report
Period
(default)
After the number of days (000 to 255, default =
000) programmed into section [3040] elapse, the
control panel can transmit the report code at the
time (00:00 to 23:59, default = 00:00)
programmed into section [3041].
ON OFF
Hourly Test
Transmission
The control panel transmits the test report code at
the same time every hour. Program the minute of
each hour (00:00 to 00:59, default = 00:00) when
the test report should be sent into section [3041].
ON ON
Timed Test
Transmission
when Armed/
Disarmed
When armed:
The control panel transmits the test report code at
regular intervals while the partition is armed.
Program the number of minutes (000 to 255,
default 005) between each transmission in
section [3042].
When disarmed:
The control panel transmits the test report code at
regular intervals while the partition is disarmed.
Program the number of minutes (000 to 255,
default = 060) between each transmission in
section [3043].
Partition 1: [3123] Partition 3: [3323] Partition 5: [3523] Partition 7: [3723]
Partition 2: [3223] Partition 4: [3423] Partition 6: [3623] Partition 8: [3823]
Section Description
[4030] Resets all the report code sections to 00 (cleared).
[4031] Sets all the report code sections to FF (defaults).
Section Sets to Defaults (FF) Reset Sections
[4032]
Zone Alarm and Restore Report Codes
Tamper and Restore Report Codes
[0201] to [0296]
[4033]
Keyswitch Arming Report Codes
Keyswitch Disarming Report Codes
Access Code Arming Report Codes
Access Code Disarming Report Codes
[0701] to [0732]
[0801] to [0832]
[2001] to [2099]
[2101] to [2199]
[4034] Special System Report Codes [3900] to [3909]
[4035]
Special Arming Report Codes
Special Disarming Report Codes
[3910] to [3919]
[3920] to [3929]
[4036] Special Alarm Report Codes [3930] to [3939]
[4037] Trouble and Restore Report Codes [3940] to [3991]