8 REFERENCE & INSTALLATION MANUALOMNIA433MHZ WIRELESS SYSTEM(OMN-RCV3)• 16 wireless zones • 16 remote controls• 500ft (152m) range line of sight•
DIGIPLEXNE CONTROL PANEL 93.1 RECOMMENDED INSTALLATION PROCEDUREThis procedure is recommended to facilitate installation by verifying thewiring at d
10 REFERENCE & INSTALLATION MANUALFigure 3-3: DigiplexNE Control Panel PCB LayoutPLEASE NOTE: When powering up the DGP-NE96 control panel (V1.02 o
DIGIPLEXNE CONTROL PANEL 113.11 CALCULATING POWER REQUIREMENTSSTEP 1: Using Table 1, calculate the total number of power units (PU) required by each d
12 REFERENCE & INSTALLATION MANUALFigure 3-4: Sample Power Requirement Calculations An LCD Keypad (80PU) can be added to the 100ft. or 300ft. wire
DIGIPLEXNE CONTROL PANEL 13Figure 3-6: Single Zone Input Connections3.14 DOUBLE ZONE CONNECTIONSEnabling the ATZ feature (see section 5.2) allows yo
14 REFERENCE & INSTALLATION MANUAL3.16 NETWORK CONNECTIONSDigiplexNE uses GuardWall technology, a specialized encryptedcommunication protocol to t
DIGIPLEXNE CONTROL PANEL 15DigiplexNE can be programmed using the following methods:4.1 WINLOAD UPLOADING/DOWNLOADING SOFTWAREWe highly recommend pr
16 REFERENCE & INSTALLATION MANUALAll detection devices connected to the control panel, keypads and zone expansion modules must be assigned to a z
DIGIPLEXNE CONTROL PANEL 175.2 ZONE DOUBLING (ATZ)(Default = disabled) The ATZ feature is a software oriented feature thatenables two detection devi
18 REFERENCE & INSTALLATION MANUALThe keypads must be assigned to the same partition as theDelayed 24Hr Fire zone for the buzzer to activate. Figu
DIGIPLEXNE CONTROL PANEL 195.5.5 Alarm Types5.5.6 Intellizone(Default = 010) If an alarm condition occurs on a zone with option [7]enabled, the cont
20 REFERENCE & INSTALLATION MANUALThe DigiplexNE control panel can support up to 32 keyswitch zones in addition to the 96 standard zones. A keyswi
DIGIPLEXNE CONTROL PANEL 216.2.4 PGM Activation (Utility Key)When option [3] is enabled, the keyswitch can activate a PGM. When akeyswitch is define
22 REFERENCE & INSTALLATION MANUAL7.1 ARMING FOLLOWS PARTITION(Default = disabled) A partition can be set to follow the arming anddisarming status
DIGIPLEXNE CONTROL PANEL 237.9.1 Auto-Arm TimerWhen Timed Auto-Arming is enabled (see section 7.9), the control panelwill attempt to arm the system
24 REFERENCE & INSTALLATION MANUAL7.15.2 No Exit Delay on Remote Arm(Default = enabled) When a user arms by using a remote control from theOmnia W
DIGIPLEXNE CONTROL PANEL 258.1 BELL/ALARM OUTPUT(Default = only option [1] enabled) When an alarm condition is detected in apartition, the control p
26 REFERENCE & INSTALLATION MANUAL8.5.1 Tamper Bypass Options(Default = enabled) With option [7] enabled in section [3034], the controlpanel will
DIGIPLEXNE CONTROL PANEL 27Figure 9-1: Event Reporting[0]Ademco Slow[3]Ademco ExpressPulse[1]Silent Knight Fast[2]SescoaDTMF(Tone)Program 2-digit (0
INTRODUCTION ...
28 REFERENCE & INSTALLATION MANUAL9.1 REPORTING ENABLED(Default = disabled) With option [3] ON in section [3036], Event Reportingis enabled. When
DIGIPLEXNE CONTROL PANEL 299.2.9 Special Disarming Report CodesWhen using one of the special disarming features listed below, the controlpanel can s
30 REFERENCE & INSTALLATION MANUAL9.3 REPORT ARMING AND DISARMINGThe following two features combine to identify when a partition should bearmed an
DIGIPLEXNE CONTROL PANEL 31programmed with the same reporting format unless they are combined witha Pager format. The first digit entered into secti
32 REFERENCE & INSTALLATION MANUAL9.11 AUTO TEST REPORTThe control panel can transmit the test report code programmed intosection [3902] every ho
DIGIPLEXNE CONTROL PANEL 3310.1 TELEPHONE LINE MONITORINGWhen enabled, the system verifies the existence of the main telephone lineonce every second
34 REFERENCE & INSTALLATION MANUALA PGM is a programmable output that toggles to its opposite state (i.e. anormally open PGM will close) when a sp
DIGIPLEXNE CONTROL PANEL 3512.1 HARDWARE RESETA Hardware Reset sets sections [0001] to [3991] to default, including theInstaller and System Master C
36 REFERENCE & INSTALLATION MANUAL12.8 SYSTEM DATE & TIMEThe System Date and Time is programmed through the User Menu, pleaserefer to Clock Lo
DIGIPLEXNE CONTROL PANEL 3712.20 NO AC FAIL DISPLAY (Default = disabled) When option [6] is enabled, the control panel will notdisplay the AC Failur
5.5.6 Intellizone ...
38 REFERENCE & INSTALLATION MANUAL13.1 INSTALLER CODE (Default: 000000) The Installer Code is used to enter the control panel'sprogramming mo
DIGIPLEXNE CONTROL PANEL 39Enable or disable the options as required for each User Access Code asshown in Figure 13-1. 13.6 PARTITION ASSIGNMENTEach
40 REFERENCE & INSTALLATION MANUALAccess Control defines the days and times people are allowed to enter andexit a site. An Access Control door use
DIGIPLEXNE CONTROL PANEL 41second screen according to the 24hr. clock (i.e. 9PM = 21:00). TheIntervals are only valid during the days programmed in
42 REFERENCE & INSTALLATION MANUALWhen option [3] is enabled, the Access Card must be presented tothe reader before the User Access Code is entere
DIGIPLEXNE CONTROL PANEL 4315.1 PANEL IDENTIFIER(Default = 0000) The Panel Identifier identifies the control panel to WinLoadbefore initiating uploa
44 REFERENCE & INSTALLATION MANUAL16.1 REGULAR ARMINGThis method is used for the everyday arming of the system. All zones withinthe partition must
DIGIPLEXNE CONTROL PANEL 4516.9 EVENT RECORD DISPLAY The Event Record Display displays the user-initiated events that occurredin the system as well
46 REFERENCE & INSTALLATION MANUALEvent Group Event Feature Group Feature Start # End #000 Zone is OK000255 = any Zone #Zone Numbers001 to 096 001
DIGIPLEXNE CONTROL PANEL 47012 Special Arming000Auto Arming 000 000Arming with WinLoad 001 001Late to Close 002 002No Movement Arming 003 003Partial
9.2.6 Access Codes Disarming ...
48 REFERENCE & INSTALLATION MANUAL022 Special Disarming000Auto Arm Cancelled 000 000One-touch Stay/Instant Disarm 001 001Disarming with WinLoad 00
DIGIPLEXNE CONTROL PANEL 49037 Trouble Restore000TLM Trouble (see NOTE 2 on page 51) 000 000AC Failure 001 001Battery Failure 002 002Auxiliary Curre
50 REFERENCE & INSTALLATION MANUAL048 Utility Key Pressed000 Key Pressed 001 to 032 001 to 032255 Any Utility Key Not Used Not Used049 Request for
DIGIPLEXNE CONTROL PANEL 51NOTE 1: NOTE 2: The TLM trouble event can only be used with the Digiplex NE control panelmodels that have two dialers.NOT
52 REFERENCE & INSTALLATION MANUALSystem EventDefault Contact ID Report Codefor sections to Default SIA Report Codefor sections to Arming with
DIGIPLEXNE CONTROL PANEL 53Bell output current limit restore 3 321 - Bell 1 restore YH - Bell RestoredBell absent restore 3 321 - Bell 1 restore YH
54 REFERENCE & INSTALLATION MANUALCID# Reporting CodeProg.ValueCID# Reporting CodeProg.ValueCID# Reporting CodeProg.ValueMEDICAL ALARMS - 100 SYST
DIGIPLEXNE CONTROL PANEL 55 ...16 ...1
56 REFERENCE & INSTALLATION MANUAL ...25 ...
DIGIPLEXNE CONTROL PANEL 57 ...31 ...
12.15 Label Broadcast ...
58 REFERENCE & INSTALLATION MANUAL ...30 ...22 ...
DIGIPLEXNE CONTROL PANEL 59 ...9 ...40 ...
60 REFERENCE & INSTALLATION MANUAL ...31 ...31 ...
DIGIPLEXNE CONTROL PANEL 61 ...25 ...25
62 REFERENCE & INSTALLATION MANUALFFC WarningsIMPORTANT INFORMATIONThis equipment complies with Part 68 of the FCC rules subpart D and CS-03. Insi
DIGIPLEXNE CONTROL PANEL 63The Seller warrants its products to be free from defects in materials and workmanship under normal use for a period of one
Printed in Canada 09/2001 DGPNE96-EI01
16.10 Scroll Restart ...
6 REFERENCE & INSTALLATION MANUALThe integrity of a security system relies not only in the performance of thecontrol panel, keypads, motion detect
DIGIPLEXNE CONTROL PANEL 7WINLOAD(UDS-2000)• User-friendly programming of Spectra, Digiplex and DigiplexNE control panels• Remote and local uploadin