paradox.comWe hope this product performs to your complete satisfaction. Should you have any questions or comments, please visit paradox.com and send u
6 Reference & Installation ManualFigure 6: Single Zone Input Connections2.14 Double Zone ConnectionsEnabling the ATZ feature (see section 4.3) all
EVO Control Panel 7Across Separate Buildings: Strip the outer jacket at one end of the shielded cable to expose the shield. In the same building as
8 Reference & Installation Manual3 Programming Methods3.1 WinLoad Uploading/Downloading Software*We recommend programming the control panel with
EVO Control Panel 94 Zone ProgrammingEnter Section [0400], then enter the number of the zone you want to programEnter the zone’s 8-digit serial and 3
10 Reference & Installation Manual4.1 Zone ProgrammingTwo different methods can be used to program zones: 4.1.1 Using section [0400]Allows you to
EVO Control Panel 114.4.8 24Hr Gas Zones*SECTION [0400]: FIRST DIGIT = 8SECTIONS [0101] TO [0196]: FIRST DIGIT = 8When a 24Hr Gas zone opens, the co
12 Reference & Installation Manual4.6.5 Alarm TypesSECTION [0400]: OPTION [2] & [6]SECTIONS [0101] TO [0196]: OPTIONS [5] & [6]4.6.6 Intel
EVO Control Panel 134.8 EOL on Hardwire ZonesSECTION [3033]: OPTION [7](default = disabled) If detection devices connected to hardwired input termin
14 Reference & Installation Manual5 Remote Control Programming5.1 Hardware Requirements5.2 Remote Control TemplateIt is possible to set up to 16
EVO Control Panel 156 Keyswitch Programming6.1 Keyswitch NumberingSECTIONS [0501] TO [0532]Keyswitch Numbering allows you to assign any hardwired i
16 Reference & Installation Manual7 Arming and Disarming Options7.1 Arming Follows Partition(default = disabled) A partition can be set to follow
EVO Control Panel 17When option [8] is enabled, access is permitted during the programmed holidays (see section 15.8 on page 36). 7.12 Auto-Arming
18 Reference & Installation Manual(default = 015) Program the duration of the keypad lockout from 001 to 255 minutes into the desired section. Pro
EVO Control Panel 198 Alarm Options8.1 Bell/alarm Output(default = only option [1] enabled) When an alarm condition is detected in a partition, the
20 Reference & Installation Manual8.5.1 Tamper Bypass OptionsSECTION [3034]: OPTION [7] (default = enabled) When enabled in section [3034], the co
EVO Control Panel 219 Event ReportingFigure 16: Event ReportingDialing Enabled/DisabledSection [3036]Option [3]Reporting Account NumbersMonitoring
22 Reference & Installation Manual9.1 Reporting EnabledSECTION [3036]: OPTION [3] (default = disabled) If enabled, the control panel verifies if a
EVO Control Panel 239.2.10 Special Alarm Report Codes9.2.11 System Trouble Codes9.2.12 System Trouble Restore CodesIf the Telephone Line Monitoring
24 Reference & Installation Manual9.3.2 Arming/Disarming Schedule Tolerance Window(default = 000) The Arming/Disarming Schedule Tolerance Window l
EVO Control Panel 25sequentially, skipping any disabled numbers and stopping once all selected telephone numbers have been reached. If the control p
EVO Control PanelTable of ContentsIntroduction... 1Features of EVO48 ...
26 Reference & Installation Manualenabled, the control panel sends the Zone Alarm Restore report codes (see section 9.2) to the monitoring station
EVO Control Panel 2710 Dialer Options10.1 Telephone Line MonitoringSECTION [3036]: OPTIONS [1] AND [2]When enabled, the system verifies the existen
28 Reference & Installation Manual11 VDMP3 Voice Module11.1 VDMP3 Installation Instructions11.2 Feature activation (PGMs)Using the VDMP3, it is p
EVO Control Panel 2912 Programmable OutputsThe control panel provides a maximum of 100 mA to PGM1 to PGM4. PGM5 is a 5A/28Vdc N.O./ N.C. relay out
30 Reference & Installation Manual13 System Settings and Commands13.1 Hardware ResetA Hardware Reset sets sections [0001] to [3991] to default. O
EVO Control Panel 3113.10 PartitioningSECTION [3031]: OPTIONS [1] TO [8](default = partition 1 enabled) The control panel can provide up to eight co
32 Reference & Installation Manual13.22 Auto Trouble ShutdownSECTION [3021](default = 00) If a trouble occurs more than the number programmed, the
EVO Control Panel 33Table 11: Russian Keypad Letter AssignmentTable 13: Hebrew Special Characters CatalogueTable 14: Russian Special Characters Cata
34 Reference & Installation Manual14 Access Codes14.1 Installer Code SECTION [1000](default = 000000) The Installer Code is six digits in length
EVO Control Panel 3514.6 Partition AssignmentSECTIONS [1002] TO [1999]: ASSIGN AREA SCREEN, OPTIONS [1] TO [8] Each of the 998 user access codes can
Reference & Installation ManualProgrammable Outputs... 29PGM Activation Event...
36 Reference & Installation Manual15 Access Control: System FeaturesFor details on connecting Access Control devices, refer to the “Digiplex Acce
EVO Control Panel 37Figure 20: Example of a Schedule Tolerance WindowThe Schedule Tolerance Window applies to Access Schedules only (see section 15.
38 Reference & Installation Manual16 WinLoad Software16.1 Panel IdentifierSECTION [3011](default = 0000) Program the same Panel Identifier in the
EVO Control Panel 39Figure 21: Upgrading Control Panels and ModulesFigure 22: Upgrading EVO641-EVO641R KeypadsTo computer’s 9-pin serial port (DB-9)
40 Reference & Installation Manual17 Appendix 1: Automatic Report Code ListSystem EventDefault Contact ID Report Codewhen using sections [4032] t
EVO Control Panel 41Zone tamper restore (##) 3 144 - Sensor tamper restore TR - Tamper RestoralKeypad Lockout 1 421 - Access denied JA - User Code T
42 Reference & Installation Manual18 Appendix 2: Contact ID Report Code ListCID# Reporting CodeProg.ValueCID# Reporting CodeProg.ValueCID# Report
EVO Control Panel 43455 Auto-Arm Failed 9E COMMUNICATION DISABLES - 550 & 560 609 Video Xmitter Active C5456 Partial Arm 9F 551 Dialer Disabled
44 Reference & Installation Manual19 Appendix 3: Keypad Installation Instructions1.1 Keypad Installation Instructions1.1.1 Connecting the Keypads
EVO Control Panel 453.1 Programming3.1.1 Entering Module Programming ModeThe keypad is programmed through the control panel. To do so, you must firs
EVO Control Panel 11 IntroductionThe Digiplex EVO is a security and access control system with 8 on-board zone inputs (16 with zone doubling) that
46 Reference & Installation Manual3.3.12 Keypad Tamper EnableSECTION [006]: OPTION [5]3.3.13 Combus Voltmeter1. From Normal Mode press and hold th
EVO Control Panel 473.5.11 Beep on TroubleSECTION [005]: OPTIONS [1] TO [4]Option [1] OFF=Beep disabled: System Troubles and Clock LossOption [1] ON
48 Reference & Installation Manual3.6.13 Beep Timer For Door Left Open AlarmSECTION [012]Enter any value between 001 and 255 to determine the numb
EVO Control Panel 494.1.5 Exit Confidential ModeSection [009] Option [2]Option [2] ON = Exit Confidential Mode by entering an access code.Option [2]
50 Reference & Installation Manual5 IndexAAC Failure not Displayed ... 32AC Power ...
EVO Control Panel 51Delay Alarm Transmission ... 12Delay Alarm Transmission Timer ...
52 Reference & Installation ManualNNo AC Fail Display ... 32No Bell Cut-Off on Fire Alar
EVO Control Panel 53Test reports ... 25Timed and Hourly Test Transmission ...
6 WarningsFCC WarningsIMPORTANT INFORMATIONThis equipment complies with Part 68 of the FCC rules subpart D and CS-03. Inside the cover of this equipm
Household Fire Warning Systems (US and Canada)• At least one model EVO641 keypad shall be used with the system.• One Paradox model MR3-UL end-of-line
2 Reference & Installation Manual2 Installation2.1 Recommended Installation Procedure1. Connect a small group of modules, including a keypad. See
CAUTION: Users should not attempt to make such connections themselves, but should contact the appropriate electrical inspection authority, or electric
Printed in Canada - 10/2007 paradox.com EVO-EI03
EVO Control Panel 3Figure 3: EVO Control Panel Wiring DiagramAUX Power (Auxiliary):Provides up to 700mA. Refer to Table 1 on page 4 When installing th
4 Reference & Installation Manual2.11 Calculating Power Requirements1. Using Table 1, calculate the total number of milliamps (mA) required by eac
EVO Control Panel 5Figure 4: Sample Power Requirement Calculations Do not use the same transformer for the control panel and the external power supp