TEST THE SYSTEM
Test the system immediately following installation and weekly for proper operation.
Test each detector by pushing the test button until a short beep is heard (approximately three seconds). Release the button. The
Detector will then test itself for proper operation and the RED LED will flash 4-6 times.
At completion of the self-test, the Detector alarm will sound 2 alarm patterns. The Detector then resumes normal operation.
If the UltraGuard 12V is connected to a furnace, during the detector test the furnace will shut down and restart.
Return to the Monitor after testing Detectors and check the panel. If the UltraGuard 12V is operating properly 
The zone lights will be on for each of the zones in which you have tested detectors
The Trouble Light will be on also.
If the reverse sequence happens, the most probable cause is that EOLRs are placed inappropriately!
With the UltraGuard 12V operating properly, press the RESET button (item j, figure 1, page 3)
CAUTION: This test should be completed prior to connecting to the alarm panel. If connected to the alarm panel
the monitoring service should be notified prior to testing.
The Detector box contains two self-adhesive labels. You should write the telephone numbers of the emergency service provider
and a qualified technician in the space provided on the labels. Place one label next to the Detector, and the other label near a
source of fresh air where you plan to gather after the Detector indicates the presence of carbon monoxide.
BURGLAR ALARM PANEL CONNECTIONS
General Considerations
All UltraGuard 12V alarm panel outputs are NC (normally closed) contacts that open on an alarm or fault/trouble condition. This
makes UltraGuard 12V compatible with any burglar panel and with fire alarm panels that have programmable (NC vs. NO)
zones. Some fire alarm panels require normally open type C contacts in which case you have to install a relay between
UltraGuard 12V and the fire alarm panel (see Fire Alarm Connection below).
The UltraGuard Monitor is a fail safe design that will Fault/Trouble on loss of power. The UltraGuard Monitor can be configured
for a Basic alarm panel or a Zoned alarm panel with the position of J6 (figure 22).
Because UltraGuard is a smart monitor, it is not necessary to place jumpers or resistors on unused zone inputs. Unused inputs
must be left un-terminated.
Burglar Alarm Connection
Zone relay outputs should only be connected to power limited circuits. Please note that CO Detector circuits are power limited,
and furnace wiring is not power limited.
Figure 22. Burglar alarmpanel connection
19