SEKURE ITI UltraGard Manual do Utilizador Página 11

  • Descarregar
  • Adicionar aos meus manuais
  • Imprimir
Vista de página 10
ZONED MODE
Figure 4 shows how the UltraGuard Monitor distributes the signals in the ZONED mode.
Z1 ALARM, Z2 ALARM, Z3 ALARM, and Z4 ALARM can output
ONLY CO ALARM signals from the corresponding input
zones ZONE 1, ZONE 2, ZONE 3 and ZONE 4.
In the Zoned mode a CO alarm signal comes from a CO Detector into a corresponding INPUT Zone and, then, is channeled to
a corresponding OUTPUT Zone, which can be output further to an alarm panel.
The TEMPERATURE and FAULT signals are sent to the alarm panel the same way in both ZONED and BASIC mode.
FAULT signals from all the CO Detector Zones are channeled into a single FAULT ANY zone for a further transmission to
an alarm panel.
The TEMPERATURE signal always communicates to ALARM ANY zone. In the ZONED mode ONLY TEMPERATURE
signal can be retrieved from ALARM ANY zone!
In order to utilize all the reporting features of the UltraGuard Monitor an alarm panel has to have as many zones available as
are employed for CO Detectors PLUS 1 for Temperature and 1 For Fault.
Example I.
There are 20 detectors installed. All four Input Zones are involved.
Scenario 1. There are 6 Zones available on the alarm panel.
All the features  CO Alarms from specific zones, temperature and faults  will be reported to the alarm panel.
Scenario 2. There are 5 Zones available on the alarm panel.
You have to decide what are the priorities in reporting. You need to drop either temperature or fault reporting.
Scenario 3. There are 4 Alarm Panel Zones available.
You will, probably, need to drop both temperature and fault reporting if you decide to use ZONED configuration so that
CO alarms are reported separately to each alarm panel zone.
Figure 4. Zoned Mode Signals Distribution
8
Vista de página 10
1 2 ... 6 7 8 9 10 11 12 13 14 15 16 ... 27 28

Comentários a estes Manuais

Sem comentários