SPECTRA SERIES 21
5.8.1 AUT O ZONE SHUTD OWN
Sections [001] to [016] = Zones 1 to 16
Option [1] OFF = Auto Zone Shutdown Disabled
Option [1] ON = Auto Zone Shutdown Enabled for selected zone (default)
If, in a single ar med period, the number of alar ms generated by a zone wi th the Auto Zone Shutdown
option enabled exceeds the number defined by the Auto Zone Shutdown Counter, the control panel wil l no
longer generate an alarm for that zone. To program the Auto Zone Shutdown Counter, key in the desired
limit (000=Disabled, 001 to 015, Default = 5) into section [089]. T he Auto Zone Shutdown Counter resets
every time the system is armed.
5.8.2 BYPASS ZONES
Sections [001] to [016] = Zones 1 to 16
Option [2] OFF = Bypass Zone Disabled
Option [2] ON = Selected Zone is Bypass Enabled (default)
When a user, util izes the Bypass Programming feature (see page 49), only zones with the Bypass option
enabled can be programmed as bypassed.
Do not program a Fire Zone with the Bypass option, as the control panel will never bypass
Fire Z ones.
5.8.3 STAY ZONES
Sections [001] to [016]: Zones 1 to 16
Option [3] OFF = Stay Zone Disabled (default)
Option [3] ON = Selected Zone is Stay Enabled
Zones with the Stay option enabled will be bypassed when the system is Stay Armed (see page 48).
Do not program a Fire Zone with th e Stay option, as the control panel will never bypass Fire
Zones when Stay Arming.
5.8.4 ALA RM TYPES
Sections [001] to [016]: Zones 1 to 16
[4] OFF / [5] OFF: Audi ble Stea dy (default)
When the conditions for an al arm have been met, the control panel can transmi t the appropriate Zone
Alarm report code (see page 31) and provides a steady output for any bells or sirens connected to the
control panel’s bell output.
[4] OFF / [5] ON: Audi ble Pulsed Alar m
When the conditions for an al arm have been met, the control panel can transmi t the appropriate Zone
Alarm report code (see page 31) and provides a pulsed output ( see Figure 5-2 on page 19) for any bells or
sirens connected to the control panel’s bell output.
[4] ON / [5] OFF: Silent Alarm
When the conditions for an alarm are met, the control panel can transmi t the appropriate Zone Alarm
report code (see page 31) and will not activate the control panel’s bell output. The appropriate AR M or
STATUS LED on the keypads will flash to indicate an alarm and the user will still have to disarm the system.
[4] ON / [5] ON: Report Only
When the conditions for an al arm have been met, the control panel can transmi t the appropriate Zone
Alarm report code (see page 31). The system will not have to be disarmed.
5.8.5 INT ELLIZONE
Sections [001] to [016]: Zones 1 to 16
Option [6] OFF = Intellizone Disabled (default)
Option [6] ON = Intellizone Enabled for Selected Zone
This feature reduces the possibility of false alarms. When a zone with the Intellizone option opens, the
panel does not immediately generate an alarm. First it triggers the Intellizone Delay Timer. To program the
Intellizone Delay Timer, key in the desired 3-di git value (010 to 255 seconds, Defaul t = 48 seconds) into
section [084]. If any of the following conditions occur during this period, the panel will generate an alarm:
• During the Intellizone Delay, a second zone has caused an alarm.
• D uring the Intellizone Delay, the zone in alarm has restored (cl osed) and re-occurred (opened).
• The zone in alarm remains open for the entire Intellizone Delay.